• The -040
level switch controller is commonly used as
a high or low level shut off with pumps or
valves. The -050 level switch controller is
commonly used for the automatic filling or
emptying of a tank between two switch points.
The single latched relay provides the automatic
pump or valve control feature. The -060 level
switch controller is commonly used for the
automatic filling or emptying of a tank between
two switch points with an additional high
or low level alarm switch point.
NRTL/C
LR 79326-4
Supply
voltage: 120/240 VAC,
50/60 Hz.
Consumption: 5
Watt.
Sensor supply: 13.5
VDC @ 27 mA.
Relay type: -040:
(1) SPDT.
-050:
(1) Latched SPDT.
-060:
(2) SPDT (1 Latched).
Relay current: 250
VAC, 10A, 1/2 hp.
Relay mode: Selectable,
NO / NC.
Time delay: 0-60
seconds.
LED indication: Sensor,
relay & power.
Fail safety: Power
fail-safe.
Temp. range: F:
-40º to 158º.
C:
-40º to 70º.
Enclosure rating: Panel
or 35 mm DIN .
Enclosure mat'l: PP,
flame retardant
(U.L. 94VO).
FEATURES
• Remote
relay controller mounts on panel or 35 mm
DIN rail. • Fail-safe relay control
for direct actuation of pumps or valves.
• Offered in 3 versions, 1, 2 or 3 switch
inputs with 1 or 2 relay outputs. •
LED indicators for sensor, relay and power
status. • Adjustable 0-60 second
time delay dampens out relay chatter.
• Invert switch provides simple NO /
NC relay operation.
SPECIFICATIONS
Part
Number
Select the configuration
Description
Output
LC40-1001
High or Low Controller
(1) 10A Relay
LC41-1001
Automatic Fill
or Empty Controller
(1) Latched 10A
Relay
LC42-1001
Automatic Fill/Empty
w/ Alarm Controller
(1) 10A Relay (1
Latched)
REMOTE ISOLATION
RELAY CONTROLLER
FEATURES
SPECIFICATIONS
• Remote
relay controller mounts on panel or 35 mm
DIN rail. • Fail-safe relay control
for direct actuation of pumps or valves.
• Offered in 3 versions, 1, 2 or 3 switch
inputs with 1 or 2 relay outputs. •
LED indicators for sensor, relay and power
status. • Adjustable 0-60 second
time delay dampens out relay chatter.
• Invert switch provides simple NO /
NC relay operation.
NRTL/C
LR 79326-4
Supply
voltage: 120/240
VAC, 50/60 Hz.
Consumption: 5
Watt.
Sensor supply: 13.5
VDC @ 27 mA.
Relay type: -024:
(1) SPDT. -025:
(1) Latched SPDT.
-026:
(2) SPDT (1 Latched).
Relay current: 250
VAC, 10A, 1/2 hp.
Relay mode: Selectable,
NO / NC.
Time delay: 0-60
seconds.
LED indication: Sensor,
relay & power.
Fail safety: Power
fail-safe.
Temp. range: F:
-40º to 158º.
C:
-40º to 70º. Enclosure rating: Panel
or 35 mm DIN.
Enclosure mat'l: PP,
flame retardant
(U.L. 94VO).
APPROVAL
The
isolation controller is approved for use with
Class I, Groups A, B, C and D; Class II, Groups
E, F and G; Class III applications in accordance
with drawing LCD1. Please consult with a Flowline
sales representative for detailed approval
information.
LEVEL SWITCHES
The following CSA approved
level switches must be packaged with
the isolation controller for use in
intrinsically safe applications.
Switch Technology
Part Number
(1)
Ultrasonic LU10-1300
Ultrasonic LU10-1400
Ultrasonic LU10-2300
Ultrasonic LU10-2400
(1) Select the specific CSA switch part
number by refering to the detailed product
descriptions.