Burtprocess.com..Neutralization Systems, High purity systems, Pump Stations
| Process Controler | 9030 & 9040 pH/ORP Controller | 5700 pH/ORP Monitor | 2720 pH/ORP Sensor |
pH & ORP Sensors
SIGNET
Click for Manufacturer Page
SIGNET 2720 PRE-AMPLIFIER
 
The Signet 2720 unity gain Pre-amplifier converts pH probe signals to a level that can be wired over a great distance on ordinary cable. The 2720 connects to the new line of Signet pH and ORP sensors with a unique twist-lock connection design. The 2720 was designed for use with any device supplying a dual 5 VDC supply including all current Signet models of pH and ORP controllers, analyzers, and transmitters. The unit is fully potted and features a 15 ft. shielded cable and easy to connect 0.75” FNPT threads for easy installation into submersible and in-line (use threaded cap P31542) applications.

 

 
SPECIFICATIONS:
Electronics Enclosure: CPVC
Operating Temperature: -4 to 185oF (-20 to 85oC)
Gain: XI (unity)
Input Power: ±4.5 to ±8VCDC Dual Supply
Input Impedance: >1011 Ohms
   
FEATURES:
Compatible with Intelek-Pro controllers & Compak transmitters
Unique mV & TC Twist-Lock connector
Submersible or in-line mountable

 

 

SPECIFICATIONS:

Part No. Description
3-2720 Unity gain pre-amplifier
P31542 Threaded cap for in-line sensor mounting

TWIST-LOCK ELECTRODES
(USE WITH 2720 PRE-AMPLIFIER)
         
SIGNET 2714 / 2716 pH ELECTRODES       SIGNET 2715 / 2717 ORP ELECTRODES
The Signet 2714 and 2716 pH Electrodes feature a combination design with measurement, reference, and temperature compensation element in one package. The plastic body construction and unique connection design makes removal and replacement of the electrodes so simple it can be done in seconds.


SPECIFICATIONS:
Construction Materials: CPVC with Viton O-rings
Junction Type: Annular double
junction porous HDPE
Response Time: 10 seconds for 98% of pH step change @ constant temperature/pressure
Temperature Range: 32 to 135oF (0 to 85oC Bulb) (10 to 85oC Flat)
Temperature Compensation: Automatic from 32 to 212oF (0 to 100oC)
   
 

SPECIFICATIONS:

Part No. Description
3-2714 Flat pH electrode
3-2716 Bulb pH electrode
3-2715 Flat ORP electrode
3-2717 Bulb ORP electrode
(for use with the Signet 2720 Pre-amplifier )
  The Signet 2715 and 2717 ORP Electrodes feature a double-junction combination electrode with unique integral ID resistor for automatic sensor recognition by the Signet 8710 pH/ORP Transmitter. The chemically resistant CPVC body, and twist-lock connection make removal and replacement of electrodes fast and simple.


SPECIFICATIONS:
Construction Materials: CPVC with Viton O-rings
Junction Material: porous HDPE
Junction Electrolyte: (front) KNO3, (rear) 4M KCI
Electrode: Platinum Rod
Reference Electrode: Ag/AgCl